barge1914
Full Member
- Posts
- 1,941
- Likes
- 3,304
Sorry more generator stuff…
Just been looking at the Honda eu10i manual. It says the earth and neutral are not referenced, ie bonded together to the frame, in which case since there would be 115V on both live and neutral instead of 240V and 0V; therefore any RCD in the circuit would not operate.
If you want the RCD in the van to work, it says, you have to get an electrician to make a connection in the generator between neutral and the frame. In which case an earth spike is strongly recommended. Presumably because now you have 240V between live and earth.
I guess if the genny was not so bonded and did not have an earth spike then the risk of a 115V shock in an unearthed situation would be less disturbing than 240V…but still not desirable!
However…I wonder if it is normal practice for earth/ neutral to be bonded within the van itself…I hope not as it poses a whole new can of worms; with a floating neutral at 115V, if neutral and earth were bonded to the van chassis that chassis without an earth spike would also appear be at 115V…(less nasty than 240V but you would still know about it if you became the bridge between chassis and the ground).
In practice you may perhaps not always be in a position to bang a spike into the ground…and may not anyway be certain adequately low resistance…which then poses a dilemma, which set of risks is best to opt for?
I have read a number of sources who say that a suitcase generator without earth/neutral bonding doesn’t need to be earthed…and Honda seem to imply this without clearly stating so…however my thinking above suggests ‘well…er maybe’ provided there is no earth/ neutral bond in the van (so that becomes a most significant question). I can’t however see any reason in either case where an earth spike would be a bad idea, I’m sure whatever fails any earth is better than none.
Has anyone with a Honda genny looked into this and know the real answers…I may just be making waves where none exist?
Also, who sells a suitable earth spike?
Just been looking at the Honda eu10i manual. It says the earth and neutral are not referenced, ie bonded together to the frame, in which case since there would be 115V on both live and neutral instead of 240V and 0V; therefore any RCD in the circuit would not operate.
If you want the RCD in the van to work, it says, you have to get an electrician to make a connection in the generator between neutral and the frame. In which case an earth spike is strongly recommended. Presumably because now you have 240V between live and earth.
I guess if the genny was not so bonded and did not have an earth spike then the risk of a 115V shock in an unearthed situation would be less disturbing than 240V…but still not desirable!
However…I wonder if it is normal practice for earth/ neutral to be bonded within the van itself…I hope not as it poses a whole new can of worms; with a floating neutral at 115V, if neutral and earth were bonded to the van chassis that chassis without an earth spike would also appear be at 115V…(less nasty than 240V but you would still know about it if you became the bridge between chassis and the ground).
In practice you may perhaps not always be in a position to bang a spike into the ground…and may not anyway be certain adequately low resistance…which then poses a dilemma, which set of risks is best to opt for?
I have read a number of sources who say that a suitcase generator without earth/neutral bonding doesn’t need to be earthed…and Honda seem to imply this without clearly stating so…however my thinking above suggests ‘well…er maybe’ provided there is no earth/ neutral bond in the van (so that becomes a most significant question). I can’t however see any reason in either case where an earth spike would be a bad idea, I’m sure whatever fails any earth is better than none.
Has anyone with a Honda genny looked into this and know the real answers…I may just be making waves where none exist?
Also, who sells a suitable earth spike?